Joint Estimation of Operational Topology and Outages for Unbalanced Power Distribution Systems (1912.04543v1)

Published 10 Dec 2019 in eess.SY and cs.SY

Abstract: An electric power distribution system is operated in several distinct radial topologies by opening and closing of system's sectionalizing and tie switches. The estimation of the system's current operational topology is a precursor to implementing any optimal control actions (during normal operation) or restorative actions (during outage condition). This paper presents a mathematical programming approach to estimate the operational topology of a three-phase unbalanced power distribution system under both outage and normal operating conditions. Specifically, a minimum weighted least absolute value estimator is proposed that uses the line flow measurements, historical/forecasted load data, and ping measurements and solves a mixed-integer linear program (MILP) to estimate the operational topology and any outaged sections simultaneously. We thoroughly validate the accuracy of the proposed approach using IEEE 123-bus and a 1069-bus three-phase multi-feeder test system with the help of numerous simulations. It is observed that the approach performs well even at high percentages of measurement errors.