Coherence in Synchronizing Power Networks with Distributed Integral Control (1703.10425v2)
Abstract: We consider frequency control of synchronous generator networks and study transient performance under both primary and secondary frequency control. We model random step changes in power loads and evaluate performance in terms of expected deviations from a synchronous frequency over the synchronization transient; what can be thought of as lack of frequency coherence. We compare a standard droop control strategy to two secondary proportional integral (PI) controllers: centralized averaging PI control (CAPI) and dis- tributed averaging PI control (DAPI). We show that the performance of a power system with DAPI control is always superior to that of a CAPI controlled system, which in turn has the same transient performance as standard droop control. Furthermore, for a large class of network graphs, performance scales unfavorably with network size with CAPI and droop control, which is not the case with DAPI control. We discuss optimal tuning of the DAPI controller and describe how inter- nodal alignment of the integral states affects performance. Our results are demonstrated through simulations of the Nordic power grid.
Sponsor
Paper Prompts
Sign up for free to create and run prompts on this paper using GPT-5.
Top Community Prompts
Collections
Sign up for free to add this paper to one or more collections.