Split PID control: two sensors can be better than one
Abstract: The traditional proportional-integral-derivative (PID) algorithm for regulation suffers from a tradeoff: placing the sensor near the sample being regulated ensures that its steady-state temperature matches the desired setpoint. However, the propagation delay (lag) between heater and sample can limit the control bandwidth. Moving the sensor closer to the heater reduces the lag and increases the bandwidth but introduces offsets and drifts into the temperature of the sample. Here, we explore the consequences of using two probes---one near the heater, one near the sample---and assigning the integral term to the sample probe and the other terms to the heater probe. The \textit{split-PID} algorithm can outperform PID control loops based on one sensor.