2000 character limit reached
An Exact Linearization Method for OLTC of Transformer in Branch Flow Model (1606.00941v1)
Published 3 Jun 2016 in cs.SY
Abstract: The branch flow based optimal power flow(OPF) problem in radianlly operated distribution networks can be exactly relazed to a second order cone programming (SOCP) model without considering transformers. However, the introdution of nonlinear transformer models will make the OPF model non-convex. This paper presents an exact linearized transformer's OLTC model to keep the OPF model convex via binary expanstion scheme and big-M method. Validity of the proposed method is verified using IEEE 33-bus test system.