Geometry of Injection Regions of Power Networks (1107.1467v4)

Published 7 Jul 2011 in math.OC, cs.IT, cs.SY, and math.IT

Abstract: We investigate the constraints on power flow in networks and its implications to the optimal power flow problem. The constraints are described by the injection region of a network; this is the set of all vectors of power injections, one at each bus, that can be achieved while satisfying the network and operation constraints. If there are no operation constraints, we show the injection region of a network is the set of all injections satisfying the conservation of energy. If the network has a tree topology, e.g., a distribution network, we show that under voltage magnitude, line loss constraints, line flow constraints and certain bus real and reactive power constraints, the injection region and its convex hull have the same Pareto-front. The Pareto-front is of interest since these are the the optimal solutions to the minimization of increasing functions over the injection region. For non-tree networks, we obtain a weaker result by characterize the convex hull of the voltage constraint injection region for lossless cycles and certain combinations of cycles and trees.